Zero Halogen, Low
Smoke (OHLS®) single core cable having enhanced
circuit integrity when exposed to fire. Tested
and approved by LPCB.

These cables are designed
for drawing into trunking and conduit where
a fire situation may pose a major hazard and
the maintenance of circuit integrity is a requirement.
To achieve optimum performance they should be
installed in metal conduit.
| Construction |
|
 |
| Conductors: |
|
Stranded plain annealed
copper wire conductor. |
| Insulation: |
|
Mica-glass
fire resistant tape covered by an extruded
layer of cross-linked Zero Halogen, Low
Smoke (OHLS®) insulating compound. |
| Physical Characteristics |
|
 |
| Voltage rating (Uo/U): |
|
600/1000V. |
| Operating temp: |
|
-40°C to +90°C
(The cable should not be flexed when
either the ambient or cable temperature
is below 0°C). |
| Min. bending radius: |
|
8 x overall diameter
of cable. |
| Standards
Achieved |
|
 |
| Circuit integrity |
|
BS 6387 categories
C, W & Z (when applied to a single cable)
Exceeds IEC 60331 - 3 hours at 750°C
- when the test temperature was increased
to 950°C, equivalent to BS 6387 Category
C. (This test was also satisfactorily applied
to Sifer cable in an earthed metal conduit,
as per LPCB guidance notes). |
| Flame propagation: |
|
IEC 60332-1, BS
EN 50265, IEC 60332-3, BS EN 50266. |
| Acid gas emission: |
|
IEC 60754-1, BS
EN 50267-2-1. |
| Smoke emission: |
|
IEC 61034, BS EN
50268. |
A full range of insulation
colours is available including green/yellow.
Sheathed versions also available. Details available
upon request.


Download Firetuf Cables Brochure |